Home Measurement Technology Pressure dependent flow elements 

Pressure dependent flow elements

Measuring orifices, nozzles and venturi tubes – overview

Subcritically operated pressure drop devices work according to Bernoulli’s principle and are designed and manufactured according to the international standard DIN EN ISO 5167. They are differential pressure transducers for the measurement of the average flow rate and the mass flow.

Pressure drop devices with suitable differential pressure transducers are used for flow measurements of liquids, gases and vapours in pure phase in pipelines. Since transducers have no movable parts and require hardly any maintenance, this reliable procedure is used preferably in chemical and technical processes.

To set up a complete measuring section, you will find additional accessories to match the flow element here

additional equipment


Main Features

  • Throat diameter d of 5 up to 500 mm
  • Diameters of DN 10 up to DN 500
  • Straight outlet: min. 2 x DN
  • Connection by flanges
  • Suction operation for free suction of atmosphere
  • Quick response time and good accuracy
  • Very good long-time stability, no moving parts

Data Sheet

SAO Inlet nozzle

SAO nozzles (Smooth Approach Orifice) are inlet nozzles for free suction of air. They are first choice with applications, where only a low pressure drop may occur during the measurement. They are designed according to VDI/VDE 2041 similar to standard Norm DIN EN ISO 5167 part 3.

SAO nozzles are suitable for the measurement of large flows of air at free suction of atmosphere, particularly if short total lengths and low remaining pressure drops are required. Due to their efficient pressure recovery they have a very low remaining pressure drop. It depends on the type of inlet and the outlet cone.

Property Functionality
Material Aluminum / Stainless Steel
Operating Pressure
Range
Std. approx. 1 - 20 mbar;
Custom configuration possible
Nominal Pressure PN 6 to PN 16
Nominal Diameter DN 10 to DN 500
Constricted Diameter d Individually customized to the requirements
calculated considering relevant standards
such as DIN ISO EN 5167 and regulations
such as VDI/VDE 2041
Pressure Loss Permanent pressure loss, depending on
opening ratio and angle of the diffuser
approx. 10 - 25 % of operating pressure
Extraction Nozzle Std. 12 mm nozzle with G1/8"
or as specified
Labeling Type plate on the flow side with:
S/N, PN, D, d, and material
Installation Directly at the entrance of a pipeline
Installation Lengths Mainly dependent on connection diameter D
at the outlet.The opening angle α of
the outlet cone is set (6 ... 12°). The length is
usually 200 to 1200 mm. The opening ratio
β=d/D should be between 0.4 and 0.8.
Straight Inlet and
Outlet Lengths
Open suction, min. 5 x D outlet

H800 Classic venturi tubes

Classic venturi tubes H800 are manufactured according to standard DIN EN ISO 5167 part 4 with flange connection or for welding. They are the first choice for the flow measurement of gases, vapours and liquids, when short length and low pressure drop are required.

Compared with other differential pressure transducers according to ISO 5167 clearly shorter straight inlet/outlet sections are required. In addition, the weight of big venturi tubes completely manufactured of sheet steel is clearly lower than the weight of comparable venturi nozzles. The remaining pressure drop is approx. 15 up to 20 % of the measured differential pressure.

Property Functionality
Material Aluminum / Stainless Steel
Operating Pressure
Range
Std. approx. 1 - 20 mbar
Custom configuration possible
Nominal Pressure PN 6 to PN 400
Nominal Diameter DN 50 to DN 1000
Constricted Diameter d Individually customized to the requirements
calculated considering relevant standards
such as DIN ISO EN 5167 and regulations
such as VDI/VDE 2041
Pressure Loss Permanent pressure loss, depending on
opening ratio and angle of the diffuser
approx. 5 - 15 % of operating pressure
Extraction Nozzle Std. 12 mm nozzle with G1/8"
or as specified
Labeling Type plate on the flow side with:
S/N, PN, D, d, and material
Installation Between flanges and welded in
horizontal, vertical, or angled pipe lines.
Entry Lengths Mainly dependent on the constrictiondiameter d.
The opening angle α of the inlet and outlet
cones is set. The length is usually
between 250 and 5000 mm.
Referring to an average opening ratio β = 0.6.
Straight Inlet and
Outlet Lengths
Min. 2.5 x D inlet and 1 x D outlet

Main Features

  • Throat diameter d of 10 up to 800 mm
  • Diameters of DN 25 up to DN 1000
  • Straight inlet/outlet: min. 2.5 x DN / 1 x DN
  • Connection by flanges or welding
  • Vacuum or pressure operation
  • Quick response time and good accuracy
  • Very good long-term stability, no moving parts

Data Sheet


Main Features

  • Throat diameter d of 10 up to 800 mm
  • Diameters of DN 25 up to DN 1000
  • Straight inlet/outlet: min. 4 x DN / 2 x DN
  • Connection by flanges or welding
  • Vacuum or pressure operation
  • Quick response time and good accuracy
  • Very good long-term stability, no moving parts

Data Sheet

DV700 Standard Nozzle

Standard nozzles DV700 are manufactured according to standard DIN EN ISO 5167 part 3 with flange connection or for welding. They are the first choice for the flow measurement of gases, vapours and liquids, when short length and low pressure drop are required.

Compared with other differential pressure transducers according to ISO 5167 clearly shorter straight inlet/outlet sections are required. In addition, the weight of big venturi tubes completely manufactured of sheet steel is clearly lower than the weight of comparable venturi nozzles. The remaining pressure drop is approx. 15 up to 20 % of the measured differential pressure.

Property Functionality
Material General construction steels               RSt37-2
Stainless steels                                  15Mo3
Unalloyed quality steels                     C22.8,
                                                            X6CrNiTi1810
Heat-resistant construction steels   16Mo3
Plastics (PP, PVC)                              13CrMo45
Operation Pressure
Range
Std. approx. 1 - 20 mbar
Custom design possible
Nominal Pressure PN 6 to PN 100
Nominal Diameter DN 50 to DN 800
Constricted Diameter d Individually calculated based on your
requirements considering relevant standards
such as DIN ISO EN 5167 and
regulations such as VDI/VDE 2041
Pressure Loss Permanent pressure loss, depending on
opening ratio β=d²/D²
approx. 10 - 15 % of working pressure
Extraction Nozzle One nozzle at the inlet and at the narrowest
cross-section. More than 2 nozzles or flushing
connections are also available upon request.
Labeling On the outer Ø of the nozzle according to
DIN 19205, additionally with batch number and
inspection stamp.
Version A End flanges pushed on and welded tight.
Application up to max. 300 °C. Negative pressure
extraction via a ring chamber.
Version B End flanges pre-welded. Radiographic testing
of the circumferential seams possible.
Application up to max. 450 °C.
Minus pressure tapping as single borehole.
Accessories Condensate traps and shut-off valves welded
on or supplied loose on request

MBL500 Orifice measuring section

Orifice measuring sections are manufactured with different differential pressure transducers as orifices or nozzles with firmly connected inlet/outlet tubes for usage even with high pressures and temperatures according to standard DIN EN ISO 5167 part 2 and 3. They meet the minimum requirements of straight inlet/outlet lengths and mechanical type according to the standard.

They are used as differential pressure transducers for the flow measurement of gases, vapours and liquids especially in small pipes up to DN 100. Exact calculation values for the flow will be provided by using calibrated sections. In addition, the possibility of replacement of the measuring module allows for an easy changing of the measuring range.

Property Functionality
Material Manufacturing in various materials and special
materials possible. In particular, in the case of
high temperatures and aggressive media,
the specific application case must be assessed.
Material
Tests
Upon request, certificates for the materials used
can be provided, e.g., according to EN 10204.
Operating Pressure
Extraction
The operating pressure is extracted at a distance
a1 and a2 from the diaphragm plate. There is
a distinction between flange pressure extraction
according to DIN 19214 and DD/2 pressure
extraction in the pipeline, where a1 equals the
pipeline diameter D and a2 equals D/2. In special
cases, the operating pressure extraction can be
norm-like as a corner extraction at the flange.
Operating Pressure
Range
Std. approx. 1 - 20 mbar; Custom design possible
Nominal Pressure PN 6 to PN 100
Nominal Diameter DN 10 to DN 200
Constricted
Diameter d
Individually calculated based on the requirements,
considering corresponding standards such as
DIN ISO EN 5167 and regulations such as
VDI/VDE 2041.
Pressure Loss Permanent pressure loss, depending on the opening
ratio d:D approx.30 - 80 % of the effective pressure
Extraction Nozzle Std. 12 mm nozzle with G1/8"i; or as specified
Labeling S/N, PN, D, d,
flow direction, and identification of the
extraction nozzles by + and -
Installation Type F Between flanges / welded in horizontal,
vertical, or angled pipe lines.
Installation Type S For welding into the pipe lines.
Dimensions as MBL 500F.
Installation Note Counter flanges, screws, and seals are not included
in the scope of delivery of a measuring section.
For the seals, the regulations regarding the medium
and operating conditions must be observed.
Seal type: smooth, recess DIN 2513 or
groove DIN 2512.
Installation Lengths depending on nominal diameter
approx. 50 to 4000 mm
Straight Inlet and
Outlet Lengths
Min. 2.5 x D inlet and 1 x D outlet
Possible Accessory Counter flanges, screws, and seals for
installation, shut-off valves, condensate vessels,
measuring line vessels, and valve blocks...

Main Features

  • Bore diameter d of 5 up to 160 mm
  • Diameters of DN 10 up to DN 200
  • Straight inlet/outlet: min. 10 x DN / 5 x DN
  • Connection by flanges
  • Vacuum or overpressure operation
  • Quick response time and good accuracy
  • Very good long-term stability, no moving parts

Data Sheet


Accessories

We also offer further measurement technology accessories for flow measurement. In addition to suitable sensors for the measuring section, complete evaluation units for plug-and-play measurements are also available.

Pressure sensors

Temperature and Humidity sensors

Measurement units